BENSHAW ENHANCED KEYPAD Información técnica Pagina 147

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 174
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 146
9 – TECHNICAL INFORMATION
Technical Specifications
141
9.6 List of Motor Protection Features
ANSI 51 – Electronic motor overload (Off, class 1 to 40, separate starting and running curves available)
ANSI 86 – Overload lockout
ANSI 51 – Overcurrent detection (Off or 50 to 800% and time 0.1 to 90.0 sec. in 0.1 sec. intervals)
ANSI 50 - Instantaneous electronic overcurrent trip
ANSI 37 – Undercurrent detection (Off or 5 to 100% and time 0.1 to 90.0 sec. in 0.1 sec. intervals)
ANSI 46 – Current imbalance detection (Off or 5 to 40%)
ANSI 51G – Ground fault detection (Off or 5 to 100%)
ANSI 48 – Adjustable up-to-speed / stall timer (1 to 900 sec. in 1 sec. intervals)
ANSI 59 / 27 – Adjustable over/under voltage protection (Off or 1 to 40%, time 0.1 to 90.0 sec. in 0.1 sec. intervals,
independent over and under voltage levels)
ANSI 47 - Phase rotation (selectable ABC, CBA, Insensitive, or Single Phase)
ANSI 81 – Over / Under Frequency
ANSI 74 – Alarm relay output available
Single Phase Protection
Shorted SCR detection