P74 Starter Type FUN 07
LED Display LCD Display
Range LED LCD Description
nor Normal Normal Reduced Voltage Soft Starter RVSS. (Default)
I d Inside Delta Inside Delta, RVSS.
Y-d Wye-Delta Wye Delta.
PctL Phase Ctl Open Loop Phase control using external analog input
reference.
cFoL Curr Follow Closed Loop Current follower using external analog input
reference.
AtL ATL Across the line. (Full Voltage)
Description The MX
2
has been designed to be the controller for many control applications; Solid State Starter, both
Normal (outside Delta) and Inside Delta, and Electro mechanical starters, Wye Delta, Across the line full
voltage starter, Phase Control/Voltage Follower, Current Follower. In each case, the MX
2
is providing the
motor protection and the necessary control for these applications.
z NOTE: For single phase operation, select Normal for the Starter Type parameter, and Single Phase for the
phase order parameter.
See Also Phase Order (P77 / FUN 04) parameter on page 126.
Theory of Operation section 7.8, Wye-Delta Operation on page 160.
Theory of Operation section 7.11, Phase Control on page 165.
Theory of Operation section 7.12, Current Follower on page 167.
124