BENSHAW ENHANCED KEYPAD Manual de usuario Pagina 171

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 222
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 170
Across The Line Starter
7.9 Across The Line (Full Voltage Starter)
When the Starter Type parameter is set to ATL, the MX
2
is configured to operate an Electro mechanical full voltage or across-the-line
(ATL) starter.
In the ATL configuration, the MX
2
assumes that the motor contactor (1M) is directly controlled by an output relay that is programmed to
RUN. Therefore, when a start command is given, the RUN programmed relay energizes the motor contactor, which applies power to the
motor. When the MX
2
determines that the motor is at full speed, the up-to-speed (UTS) condition is indicated by energizing the UTS
programmed relays. When configured as an ATL starter, all MX
2
motor and starter protective functions, except bad SCR detection and
power stack overload, are available to provide full motor and starter protection.
z NOTE: When in ATL mode, the acceleration ramp, kick, and deceleration parameter settings have no effect on motor operation.
z NOTE: When in ATL mode, the SCR gate outputs are disabled.
163
7 - THEORY OF OPERATION
START
Starters
stop
reset
enter
menu
MX2 CARD
BIPC-300055-01
Figure 43: A Typical ATL Starter Schematic with the MX
2
Vista de pagina 170
1 2 ... 166 167 168 169 170 171 172 173 174 175 176 ... 221 222

Comentarios a estos manuales

Sin comentarios