To order WEB STOCKED items: visit www.BenshawExpress.com
2 - 5
sg series
VARIABLE TORQUE / STANDARD DUTY / HEAVY DUTY
Standard Low Voltage Drive Products
Sensorless Vector Drives
RATINGS
Variable Torque:
7.5–40 HP @ 230 V
7.5–700 HP @ 460 V
7.5–400 HP @ 600 V
Standard Duty:
7.5–40 HP @ 230 V
7.5–600 HP @ 460 V
7.5–400 HP @ 600 V
Heavy Duty:
5–30 HP @ 230 V
5–500 HP @ 460 V
5–300 HP @ 600 V
Highlights:
The SG series is a compact, economical drive designed for the most
demanding applications. The flexible power stack allows the user to
apply it to heavy duty loads (150% for 60 secs), standard duty loads
(120% for 60 secs), or variable torque loads (110% for 60 secs).
With over 250 programmable parameters, Benshaw’s SG series
drives are configurable to meet the needs of almost any industrial ap-
plication, yet remain simple and easy to use.
Key Advantages:
• Standard and heavy duty ratings
• Integral PID Control
• Sensorless vector control or
V/Hz control
• Integral multiple motor control for
pumping applications
• Uploadable / downloadable keypad
• Flexible, programmable I/O
• Economical, compact design
• Simple, easy to use LCD interface
• Standard ModBus RTU port
• Windows-based software
Standard Features:
• Standard I/O: 8 digital inputs,
2 analog inputs, 2 analog outputs,
5 relay outputs
• Optional I/O: Isolated analog
output board (adds 2 additional
analog outputs, 0/4 – 20 mA)
• Digital metering: Output currents,
ground current, output frequency,
DC link voltage, motor RPM, output
motor voltage, run time, and more
• Protection: Over current, ground
fault, over voltage, current limit,
motor overload, phase loss, over
heat, loss of signal and more
• Analog inputs: 1 at 0/4 – 20 mA,
1 at 0 – 10 Vdc (or -10 to 10 Vdc)
• Communications: Modbus RTU
(standard). Optional Fieldbus
includes DeviceNet, Profibus,
BacNet, LonWorks, Modbus TCP
• Voltage tolerance: -15%, +10%
• Control methods: V/Hz, sensorless
vector, slip compensation
• V/Hz patterns: Linear, squared,
user programmable V/Hz
• Analog outputs: 2 at 0 – 10 Vdc
(standard), 2 at 0/4 – 20 mA (with
option board). Configurable to
motor speed, output current,
output voltage, DC link voltage,
power, PID follower
• Relay outputs: 1 Form C fault
relay output, 4 Form A relay
outputs configurable to running,
faulted, ready, at speed, high or
low frequency levels, loss of signal,
ready, and more
• Digital inputs: 8 digital inputs
configurable to forward run, reverse
run, 3 wire start / stop, reset, jog,
preset speeds, motorized pot
function, external trip, alternate
ramp selections, HOA, and more
• User interface: 2 line LCD display,
16 characters per line
• Stop methods: Coast, decel, DC
injection braking, Flux braking and
optional dynamic braking