BENSHAW ENHANCED KEYPAD Manual de usuario Pagina 48

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 132
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 47
2 - 32
To order: call 412-968-0100
Standard Low Voltage Drive Options
Dynamic Brake Resistors and Brake Modules
Dynamic brake resistors and modules are used to address over
voltage conditions with drives. Over voltage trips occur when the DC
bus in the drive increases to the over voltage trip level. This increase in
voltage occurs when the mechanical energy in the motor is converted
into regenerative electrical energy, which is transferred back into the
drive (the motor acts like a generator).
Regeneration occurs when:
• Thedecelerationtimeistooquick.
• Theloadhashighinertiaandkeepsrotatingafterthedriveoutput
power has decreased below that of the load.
(Ex: fly wheels, large fans)
• Theloadisanoverhaulingload,cyclicalorperiodic.
(Ex: pump jack, punch press)
• Whenthemotorsuddenlybecomesunloaded.
(Ex: lumber mill saw applications)
Regeneration can occur on an occasional basis or periodically
(cyclical) depending on the type of load. A dynamic brake module
and resistor are required to be added to the drive to dissipate this
excess power. The module and resistor must be sized correctly
depending on the application.
Contact Benshaw for assistance with sizing brake resistors
and brake modules.
Vista de pagina 47
1 2 ... 43 44 45 46 47 48 49 50 51 52 53 ... 131 132

Comentarios a estos manuales

Sin comentarios